3-Pipe FSV-EX MF3 Series
NO ROOM TO ADD MORE PRODUCTS
The wishlist has already reached the maximum number of products
3-Pipe FSV-EX MF3 Series
For simultaneous heating and cooling
Features
Cooling/Heating kW (rated) |
22.4/25.0 |
28.0/31.5 |
33.5/37.5 |
40.0/45.0 |
45.0/50.0 |
Cooling/Heating Btu/h (rated) |
76,500/85,300 |
95,600/107,500 |
114,300/128,000 |
136,500/153,600 |
153,600/170,600 |
Model No. |
U-8MF3R7 |
U-10MF3R7 |
U-12MF3R7 |
U-14MF3R7 |
U-16MF3R7 |
|
|
|
|
|
Simultaneous Heating and Cooling Operation
・ Office buildings with diverse room temperatures due to the different amounts of direct sunlight received
・ Buildings with computer/business equipment rooms requiring year-round cooling
・ Hotels and other facilities where heating and cooling are used simultaneously
Extraordinary Energy-Saving Performance
Key Technologies for Excellent Energy Savings
Multiple Large-capacity All-Inverter Twin Compressors
Enlarged Heat Exchanger Surface Area
Energy Saving and Comfortable Air Conditioning
Oil Management System for Energy Saving and Comfortable Air Conditioning
Variable Evaporation Temperature (VET) for Energy Saving and Comfortable Air conditioning
The indoor and outdoor units work in tandem to control evaporation temperature, refrigerant volume, and airflow. This enables optimal air conditioning according to the number of people in the room and the indoor temperature, as well as energy savings and comfort.
Note: When fan speed is set to Auto.
Demand Response Ready
Simple Demand Response
**Current input is DC 24V 10mA Use a very small electric current contact point for the relay.
Flexible Demand Response
High Durability
Extended Operating Range
Note: Cooling/heating capacity depend on indoor/outdoor temperature. Please refer technical databook.
Rust-resistant and Easy to Maintain
Reliable Operation
Extended Compressor Life by Uniform Compressor Operation Time
Automatic Backup Operation in the Case of Compressor Failure or Outdoor Unit Malfunction
Highly Flexible Installation and Design
・ Actual piping length 200 m.
・ Elevation difference of maximum 50 m in case of outdoor unit is higher than indoor unit.
・ Maximum 15 meters height difference between indoor units.
・ Up to 40 m piping after first branch.
・ Up to 52 indoor units connectable.
・ Connectable maximum allowable indoor / outdoor capacity ratio up to 150%.
・ External static pressure of 80 Pa.
Specs
- R410A
- Inverter
- DRED ready
- Heat Recovery
Wide range of systems from 8 HP to 48 HP
Class-leading COP of 4.87 (cooling) and COP of 5.09 (heating) (for 8 HP model)
Cooling operation possible with outdoor temperatures as high as 52˚C (DB)
Operating range to provide heating at outdoor temperatures as low as -20˚C WB
Long maximum piping length (up to 500 m)
Up to 52 indoor units connectable